Zhengzhou No. 2 Cable Factory
Main products:Cable,Wire,ACSR,Power Cable,XLPE Cable
Products
Contact Us
  • Contact Person : Mr. JS JINSHUI
  • Company Name : Zhengzhou No. 2 Cable Factory
  • Tel : 086-0371-67849797
  • Address : Henan,Zhengzhou,No. 82, West Part of Kexue Avenue, High and New Technology Development Zone, Zhengzhou City, Henan Province. China
  • Country/Region : China
  • Zip : 450001

aluminum conductor AAC,AAAC,ACSR wire

aluminum conductor AAC,AAAC,ACSR wire
Product Detailed
ACSR bare conductor, or ACSR bare wire XLPE,PE,PVC insulation AAC, ACCR, AAAC, ACSR conductor aluminium conductor steel core

ACSR overhead cable

All Aluminum Conductor(AAC)& Aluminum Conductor Steel Reinforced(ACSR))for ASTM (AAC, ACCR, AAAC, ACSR) Generally Confirming to IS 398 (Part-I, II, IV), IEC-228 (AAAC) Conductor as per ASTM-B-399-1992 (AAAC) Conductor as per BS-3242-1970 (AAAC) Conductor IS: 398-IV-1994 (ACSR) as per ASTM-B-233-1992 (AAC) as per BS-215-1-1970 (AAC) as per IS-398-1: 1976 (AAC) as per ASTM-B-231-1990 (ACSR) as per IS: 398-II: 1976 & IS: 398-V: 1992 (ACSR) BS-215-II-1970 (AACSR) as per IEC-1089-1191 AAC(All aluminum conductor) are suited for overhead power line. We can supply this conductor according to different recognized standards, such as IEC61089, BS215, BS EN 50182: 2001, ASTM B231, CSA C49, DIN480201, JIS C3109.Specifications ACSR bare conductor meets or exceeds the following ASTM specifications: B-230 Aluminum Wire, 1350-H19 for Electrical Purposes B-231 Aluminum Conductors, Concentric-Lay-Stranded B-232 Aluminum Conductors, Concentric-Lay-Stranded, Coated Steel Reinforced (ACSR) B-341 Aluminum-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ) B-498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR/AZ) B-500 Zinc Coated and Aluminum Coated Stranded Steel Core for Aluminum Conductors, Steel Reinforced (ACSR) Notes Resistance is calculated using ASTM standard increments of stranding and metal conductivity of 61.2% IACS for EC (1350) and 8% IACS for steel. AC (60Hz) resistance includes current dependent hysteresis loss factor for 1 and 3 layer constructions. Current ratings are based on 75oC conductor temperature, 25oC ambient, 2ft/s wind, 96/watts/sq. Ft sun, 0.5 coefficients of emissivity and absorption.The data sheets below show part spec of IEC61089

Code Number

Stranding&Wire Diameter

Approx Overall

Sectional Area

ApproxWeight

Breaking Load

DC Resistance

Al

Steel

Diameter

Al

Steel

Total

mm

mm

mm

mm 2

mm 2

mm 2

Kg/km

KN

Ohm/km

16

6/1.84

1/1.84

5.53

16

2.67

18.7

64.6

6.08

1.7934

25

6/2.30

1/2.30

6.91

25

4.17

29.2

100.9

9.13

1.1478

100

6/4.61

1/4.61

13.8

100

16.7

117

403.8

34.33

0.2869

125

18/2.97

1/2.97

14.9

125

6.94

132

397.9

29.17

0.2304

160

18/3.36

1/3.36

16.8

160

8.89

169

509.3

36.18

0.18

250

22/3.80

7/2.11

21.6

250

24.6

275

880.6

68.72

0.1154

400

54/3.07

7/3.07

27.6

400

51.9

452

1510.3

123.04

0.0723

450

54/3.26

7/3.26

29.3

450

58.3

508

1699.1

138.42

0.0643

500

54/3.43

7/3.43

30.9

500

64.8

565

1887.9

153.8

0.0578

560

54/3.63

19/2.18

32.7

560

70.9

631

2103.4

172.59

0.0516

630

54/3.85

19/2.31

34.7

630

79.8

710

2366.3

191.77

0.0459

710

54/4.09

19/2.45

36.8

710

89.9

800

2666.8

216.12

0.0407

800

72/3.76

7/2.51

37.6

800

34.6

835

2480.2

167.41

0.0361

900

72/3.99

7/2.66

39.9

900

39.9

939

2790.2

188.33

0.0321